Cummins DG Sets · 2000 kVA

Cummins C2000 D5 P — 2000 kVA Diesel Generator

Large manufacturing plants — at Motherson's Chakan plant we engineered and erected the 30 m exhaust stack serving the plant's own 2000 kVA set

Rating2000 kVA prime
ModelC2000 D5 P
Emission normMoEFCC >800 kW
EngineQSK 60 G4

What it powers

Large manufacturing plants — at Motherson's Chakan plant we engineered and erected the 30 m exhaust stack serving the plant's own 2000 kVA set

Campus and plant standby where one machine must carry the entire essential bus without paralleling

Anchor set in synchronised banks feeding MW-class loads, with Masterless Load Demand printed standard on the PowerCommand controller

Ratings this size are engineered purchases, not catalogue picks — load profile, redundancy and synchronisation decide the configuration. Send the load list and we size it free.

Specification

Genset

Model
C2000 D5 P
Prime rating
2000 kVA
Voltage · frequency
415 V · 50 Hz
Phases · power factor
3-phase · 0.8 PF
Speed
1,500 RPM
Emission norm
MoEFCC >800 kW
Controller
PCC3.3 with AMF

Engine

Make · model
Cummins QSK 60 G4
Certified power
2,319 HP
Cylinders
16, Vee
Bore × stroke
159 × 190 mm
Displacement
60.2 L
Compression ratio
14.5:1
Aspiration
Turbocharged - LTA Aftercooled
Cooling
Water cooled
Fuel
High Speed Diesel
Coolant capacity
621 L

Alternator

Make
Stamford
Frame
S7L1D-G4
Enclosure · insulation
IP 23 · Class H
Voltage regulation
±0.5%
Winding pitch
2 / 3 Pitch

Open genset dimensions

Dimensions (L × W × H)
5,950 × 2,594 × 3,304 mm
Wet weight
17,333 kg
Fuel tank
990 L

Fuel consumption

At 75% load
291 L/hr
At 100% load
390 L/hr

Source: the Cummins technical annexure for the C2000 D5 P · PSBU Rev-5 (07/2021). Diesel SG 0.85 per IS:1460; tolerance +5%. Actual consumption varies with load profile and site conditions.

Transcribed from the Cummins India technical document for the C2000 D5 P. Ratings are prime power per ISO 8528; site conditions can derate output. Manufacturers revise documents — the current Cummins datasheet and your work order govern; ask us for the current sheet. Dimensions are for the open set; acoustic treatment is engineered per site.

Above 800 kW

Engines above 800 kW sit outside CPCB IV+ under the MoEFCC's separate standards — with their own stack-height regime (30-metre class structures), acoustic treatment engineered per site rather than a factory canopy, and consent conditions that decide the installation. We have delivered exactly this — six 1010 kVA sets with three 30 m stacks for the Reserve Bank of India — and the installation engineering is part of the offer, not an afterthought.

Buying, the way we run it

One purchase order: supply, installation, testing, commissioning.

  • Sized from your load list — starting current and step loads, not nameplate totals
  • Installation engineering included in the offer — foundations, exhaust, cabling, panels
  • Commissioned on load, handed over with documentation
  • Serviced afterwards by the team that runs its own 80-set fleet

2000 kVA, answered

Frequently asked questions

Is this the prime-rated or standby-rated 2000 kVA Cummins?

This page is the prime-rated C2000 D5 P on the QSK60 G4 engine — varying load, unlimited hours per ISO 8528 with the 10% overload allowance. Cummins India has also published a standby-rated C2000 D5 on the KTA50-G21, a different machine with a narrower duty envelope. Ask any vendor which one their quote actually is.

Can the 2000 kVA set supply high-tension voltage?

Yes — the Cummins sheet lists 415 V standard with 3.3 kV, 6.6 kV and 11 kV options, factory-configured with HT alternator frames (Class F insulation on HT). HT supply brings transformer, switchgear and protection engineering into the project scope — which is exactly the turnkey work we quote alongside the set.

What fuel consumption does the sheet print for 2000 kVA?

For the radiator-cooled configuration: 291 L/hr at 75% load and 390 L/hr at full load, on diesel of 0.85 specific gravity per IS:1460 with a +5% tolerance. The standard scope includes a 990-litre free-standing external tank — at this burn rate, bulk fuel storage and day-tank design are part of the installation, and we engineer them.

Which emission rules govern a 2000 kVA genset?

Above 800 kW the set sits outside CPCB IV+ — the MoEFCC’s separate large-engine standards apply, and the stack is its own engineered structure under the >800 kW rule (maximum of 14×Q^0.3, building plus 6 m, or 30 m). Consent conditions decide the final installation; the compliance engineering is included in our turnkey scope.