Cummins DG Sets · 2250 kVA

Cummins C2250 D5 P — 2250 kVA Diesel Generator

MW-class industrial and infrastructure loads, run as a single prime-rated set or as a synchronised pair sharing one bus

Rating2250 kVA prime
ModelC2250 D5 P
Emission normMoEFCC >800 kW
EngineQSK 60 G8

What it powers

MW-class industrial and infrastructure loads, run as a single prime-rated set or as a synchronised pair sharing one bus

High-tension sites — the sheet lists factory HT options at 3.3, 6.6 and 11 kV on this rating, with HT alternator frames

Continuous-process plants that need prime-rated headroom above 2000 kVA without stepping to a multi-set bank

Ratings this size are engineered purchases, not catalogue picks — load profile, redundancy and synchronisation decide the configuration. Send the load list and we size it free.

Specification

Genset

Model
C2250 D5 P
Prime rating
2250 kVA
Voltage · frequency
415 V · 50 Hz
Phases · power factor
3-phase · 0.8 PF
Speed
1,500 RPM
Emission norm
MoEFCC >800 kW
Controller
PCC3.3 with AMF

Engine

Make · model
Cummins QSK 60 G8
Certified power
2,603 HP
Cylinders
16, Vee
Bore × stroke
159 × 190 mm
Displacement
60.2 L
Compression ratio
14.5:1
Aspiration
Turbocharged - LTA Aftercooled
Cooling
Water cooled
Fuel
High Speed Diesel
Coolant capacity
621 L

Alternator

Make
Stamford
Frame
S7L1D-H4
Enclosure · insulation
IP 23 · Class H
Voltage regulation
±0.5%
Winding pitch
2 / 3 Pitch

Open genset dimensions

Dimensions (L × W × H)
6,175 × 2,494 × 3,115 mm
Wet weight
18,976 kg
Fuel tank
990 L

Fuel consumption

At 75% load
331 L/hr
At 100% load
441 L/hr

Source: the Cummins technical annexure for the C2250 D5 P · PSBU Rev-5 (07/2021). Diesel SG 0.85 per IS:1460; tolerance +5%. Actual consumption varies with load profile and site conditions.

Transcribed from the Cummins India technical document for the C2250 D5 P. Ratings are prime power per ISO 8528; site conditions can derate output. Manufacturers revise documents — the current Cummins datasheet and your work order govern; ask us for the current sheet. Dimensions are for the open set; acoustic treatment is engineered per site.

Above 800 kW

Engines above 800 kW sit outside CPCB IV+ under the MoEFCC's separate standards — with their own stack-height regime (30-metre class structures), acoustic treatment engineered per site rather than a factory canopy, and consent conditions that decide the installation. We have delivered exactly this — six 1010 kVA sets with three 30 m stacks for the Reserve Bank of India — and the installation engineering is part of the offer, not an afterthought.

Buying, the way we run it

One purchase order: supply, installation, testing, commissioning.

  • Sized from your load list — starting current and step loads, not nameplate totals
  • Installation engineering included in the offer — foundations, exhaust, cabling, panels
  • Commissioned on load, handed over with documentation
  • Serviced afterwards by the team that runs its own 80-set fleet

2250 kVA, answered

Frequently asked questions

Is the Cummins 2250 kVA rating prime or standby?

This page is the prime-rated C2250 D5 P on the QSK60 G8 — varying load, unlimited hours per ISO 8528, 10% overload per ISO 3046. Cummins India has also published a standby-rated C2250 D5S on the QSK60 G4; the two are different machines with different duty envelopes, so always confirm the rating basis printed on the offer.

Can the 2250 kVA set be paralleled with other gensets?

Yes — the PowerCommand PC 3.3 controller ships with Masterless Load Demand printed standard on this rating, and synchronising is how most 2250 kVA installations actually run: paired sets sharing one bus, capacity added in steps, one machine serviceable while the rest carry the site. Our panels practice engineers the bus, breakers and protections.

What does the 2250 kVA set consume at load?

The Cummins sheet prints 331 L/hr at 75% load and 441 L/hr at full load for the radiator-cooled configuration, on 0.85 SG diesel per IS:1460 with +5% tolerance. Fuel logistics at this scale — bulk storage, transfer pumps, day tanks — are engineered as part of the turnkey installation, not left to the operator.

What compliance work does a 2250 kVA installation involve?

The set sits above 800 kW, outside CPCB IV+, under the MoEFCC’s separate large-engine standards — which bring the engineered stack rule (maximum of 14×Q^0.3, building plus 6 m, or 30 m), site acoustic treatment instead of a factory canopy, and consent conditions that govern the final design. All of it is in our turnkey scope.