Tools · Sizing
What size DG set do you need?
List the loads, mark how each motor starts, and get an honest rating — sized for starting current, snapped to the real fleet ladder, and confirmed free by an engineer before you commit.
| Load | Power | Unit | Qty | Type / starting method | Remove |
|---|
Indicative sizing for 415 V, 50 Hz, three-phase loads at 0.8 power factor. It does not model harmonics (UPS/VFD-heavy sites), altitude or ambient derating, or phase imbalance — an engineer confirms the final rating free of charge before any order.
How the maths works
- Running load. Every load's kW (HP × 0.746) is summed and converted to kVA at 0.8 power factor — the ISO 8528 genset rating convention.
- Continuous headroom. The set is sized so running load sits near 75% of its prime rating: ISO 8528-1 caps a prime-rated set's 24-hour average load factor at 70%, and sustained running below ~30% risks wet stacking (Caterpillar's underloading guidance) — too big is also wrong.
- Starting check. The largest motor is assumed to start last against the rest of the running load. Starting draws a multiple of full-load apparent power — about 7× for direct-on-line (high-efficiency motors can spike higher), ~3× on star-delta, ~3.5× on a soft starter at typical current-limit settings, ~1.5× on a VFD — and the surge must fit within roughly 1.75× the alternator's rating at an acceptable ~25% voltage dip (Stamford AGN090).
- Snap to the ladder. Whichever requirement governs is rounded up to the nearest rating in the actual fleet, linked to its full Cummins specification.
Worked example
A warehouse runs 12 kW of lighting and sockets plus a 20 HP (14.9 kW) direct-on-line compressor. Running load: (12 + 14.9) kW ÷ 0.8 = 33.6 kVA. Headroom check: 33.6 ÷ 0.75 = 44.9 kVA. Starting check: the compressor's surge is 14.9 ÷ 0.8 × 7 = 130.5 kVA on top of 15 kVA already running — 145.5 kVA total, which needs 145.5 ÷ 1.75 = 83.2 kVA of alternator. Starting governs, so the answer is not a 50 kVA set but the next rating above 83.2 — a 100 kVA set. This is why "just add up the kW" undersizes motor-heavy sites.
Sizing, answered
Frequently asked questions
Why does the calculator ask how each motor starts?
Because starting current — not running load — usually decides the rating. A direct-on-line motor draws roughly six times its full-load current for a few seconds; a star-delta starter cuts that to about a third; a VFD nearly eliminates it. Two sites with identical running loads can need very different gensets.
Why is the recommended set bigger than my total load?
Two reasons: a genset should not run continuously at the top of its prime rating (sizing so running load sits near 70–80% leaves margin for surges and future loads), and the set must absorb the largest motor’s starting surge without a damaging voltage dip. The calculator sizes for both and picks whichever governs.
Is this calculation enough to place an order?
No — treat it as a well-informed starting point. UPS and VFD loads add harmonics that can call for an oversized alternator, altitude and ambient temperature derate output, and phase balance matters on mixed loads. Send the load list on WhatsApp and an engineer confirms the sizing free of charge, the same day.
Can a genset be too big for my load?
Yes, and it is an expensive mistake twice over. Cummins application guidance is not to run a diesel set below about 30% of rated load for sustained periods: chronic light running glazes cylinder bores and passes unburnt fuel into the exhaust (wet stacking), which shows up later as slobber, fouled injectors and shortened life. If your genuine running load is small, size honestly and plan periodic loaded runs — or a load bank — rather than buying headroom you will never use.
Does the order in which loads start change the size I need?
Dramatically. Starting everything in one step forces the set to swallow every surge at once; stepped starting — largest motor first, then the rest — usually allows the smallest set for the same steady load. Two rules from Cummins application practice: life-safety loads may have to be up within about ten seconds of mains failure, and any motor that cycles on and off in service must be checked as if it starts last, with everything else already running.
Which loads deserve special caution?
Three families. Lightly loaded UPS systems with input filters can present a leading power factor, which a genset tolerates only in small doses before voltage control suffers — sequence lagging loads on first. Regenerative loads (lifts, cranes, hoists) push braking energy back at the set; unlike the grid, a genset can absorb very little, so other connected loads must soak it up. And rectifier-fed loads — UPS, battery chargers, VFDs — distort the waveform, calling for a larger alternator than the arithmetic suggests. Growth counts too: size for the load list you will have, not the one you have today.
Reply within 4 working hours. Engineered offer within 24 hours.