Cummins DG Sets · 2500 kVA

Cummins C2500 D5S — 2500 kVA Standby Generator

Standby cover for utility-fed plants with a reliable grid and defined outage exposure — the duty this rating is certified for

Rating2500 kVA standby
ModelC2500 D5S
Emission normMoEFCC >800 kW
EngineQSK 60 G8

What it powers

Standby cover for utility-fed plants with a reliable grid and defined outage exposure — the duty this rating is certified for

N+1 emergency capacity at large campuses, paired with prime-rated sets that carry the routine running

One step below our range-topping 2750 kVA standby set — often the availability sweet spot at MW scale

Ratings this size are engineered purchases, not catalogue picks — load profile, redundancy and synchronisation decide the configuration. Send the load list and we size it free.

Specification

Genset

Model
C2500 D5S
Standby rating
2500 kVA
Voltage · frequency
415 V · 50 Hz
Phases · power factor
3-phase · 0.8 PF
Speed
1,500 RPM
Emission norm
MoEFCC >800 kW
Controller
PCC3.3 with AMF

Engine

Make · model
Cummins QSK 60 G8
Certified power
2,875 HP
Cylinders
16, Vee
Bore × stroke
159 × 190 mm
Displacement
60.2 L
Compression ratio
14.5:1
Aspiration
Turbocharged - LTA Aftercooled
Cooling
Water cooled
Fuel
High Speed Diesel
Coolant capacity
621 L

Alternator

Make
Stamford
Frame
P1734H
Enclosure · insulation
IP 23 · Class H
Voltage regulation
±0.5%
Winding pitch
2 / 3 Pitch

Open genset dimensions

Dimensions (L × W × H)
6,175 × 2,494 × 3,115 mm
Wet weight
16,546 kg
Fuel tank
990 L

Fuel consumption

At 75% load
368 L/hr
At 100% load
496 L/hr

Source: the Cummins technical annexure for the C2500 D5S · PSBU Rev-2 (22/07/2019). Diesel SG 0.85 per IS:1460; tolerance +5%. Actual consumption varies with load profile and site conditions.

Transcribed from the Cummins India technical document for the C2500 D5S. Ratings are prime power per ISO 8528; site conditions can derate output. Manufacturers revise documents — the current Cummins datasheet and your work order govern; ask us for the current sheet. Dimensions are for the open set; acoustic treatment is engineered per site.

Above 800 kW

Engines above 800 kW sit outside CPCB IV+ under the MoEFCC's separate standards — with their own stack-height regime (30-metre class structures), acoustic treatment engineered per site rather than a factory canopy, and consent conditions that decide the installation. We have delivered exactly this — six 1010 kVA sets with three 30 m stacks for the Reserve Bank of India — and the installation engineering is part of the offer, not an afterthought.

Buying, the way we run it

One purchase order: supply, installation, testing, commissioning.

  • Sized from your load list — starting current and step loads, not nameplate totals
  • Installation engineering included in the offer — foundations, exhaust, cabling, panels
  • Commissioned on load, handed over with documentation
  • Serviced afterwards by the team that runs its own 80-set fleet

2500 kVA, answered

Frequently asked questions

Why is the 2500 kVA Cummins a standby rating?

Cummins India publishes the C2500 D5S as Standby Power per ISO 8528 — the sheet defines it for varying load during interruption of a reliable utility source, for a maximum of 500 hours per year. If your site needs prime or continuous duty at this scale, the honest engineering answer is usually a synchronised bank of prime-rated sets, and we quote both ways.

What is the largest generator Power Solutions supplies?

Our range runs one step higher — the standby-rated C2750D5B at 2750 kVA on the QSK60-G22. Beyond single sets, the answer is a synchronised bank of prime-rated machines on one bus, which is how MW-scale sites usually run anyway, for redundancy as much as capacity. Tell us the duty and we quote both ways.

What does the 2500 kVA set consume on load?

The Cummins sheet prints 368 L/hr at 75% load and 496 L/hr at full load for the radiator-cooled configuration, on diesel of 0.85 specific gravity per IS:1460, +5% tolerance. At roughly 500 litres an hour flat out, fuel storage, transfer and day-tank engineering are a core part of the installation design — included in our turnkey scope.

Which rules govern a 2500 kVA genset installation?

Above 800 kW the set is outside CPCB IV+ — the MoEFCC’s large-engine standards govern, the stack is an engineered structure under the >800 kW rule (maximum of 14×Q^0.3, building plus 6 m, or 30 m), acoustic treatment is designed per site, and your consent to operate has the final word. We deliver the compliance engineering with the set.

Related

Reply within 4 working hours. Engineered offer within 24 hours.