DG Rental · 750 kVA

750 kVA Diesel Generator on Rent

An IT campus building — chillers, UPS input and lift banks — on a single 750 kVA set.

Rating750 kVA / 600 kWe
ModelCI 750D5P
Emission normCPCB IV+
Noise75 dBA @ 1 m

What it powers

An IT campus building — chillers, UPS input and lift banks — on a single 750 kVA set.

A large cold store or food-processing plant on round-the-clock standby.

Paired and synchronised for loads that have outgrown any single mid-range rating.

Size for starting current, not running load — direct-on-line motor starting draws six to seven times full-load current. Send us your load list and we size it free of charge.

Specification

Genset

Model
CI 750D5P
Prime rating
750 kVA / 600 kWe
Full-load current
1,043 A
Voltage · frequency
415 V · 50 Hz
Phases · power factor
3-phase · 0.8 PF
Speed
1,500 RPM
Emission norm
CPCB IV+
Controller
PS0602 with AMF

Engine

Make · model
Cummins QSK19-G30
Certified power
888 HP
Cylinders
6, In-line
Bore × stroke
159 × 159 mm
Displacement
19 L
Compression ratio
14.7:1
Aspiration
Turbocharged, Charge Air Cooled
Cooling
Liquid Cooled (EG Compleat 50:50)
Fuel
High Speed Diesel
DEF
AUS 32 (Premix) as per ISO 22241
Starting system
24 V DC Electrical
Lube oil spec
CK4
Coolant capacity
95 L
Performance class
ISO 8528-5 G2

Alternator

Make
STAMFORD (CGT)
Frame
HCI634W
Enclosure · insulation
IP 23 · Class H
Voltage regulation
±1%
Winding pitch
2/3

Acoustic enclosure

Dimensions (L × W × H)
6,800 × 2,050 × 2,900 mm
Wet weight
10,200 kg
Fuel tank
990 L
DEF tank
139 L
Noise level
75 dBA (1 m, 75% load, free-field (MoEF/CPCB))

Transcribed from the Cummins India specification sheet for the CI 750D5P. Ratings are prime power per ISO 8528; site conditions can derate output — confirm against your load list.

Rental, the way we run it

Rates move with tenure, site and season — so we quote same-day, not never.

  • Acoustic-enclosed set, delivered and commissioned
  • Scheduled B-check maintenance every 250–300 running hours, included
  • 4–6-hour breakdown response on live contracts

750 kVA, answered

Frequently asked questions

What does a 750 kVA generator run?

A 750 kVA (600 kW) set carries an IT campus building — chillers, UPS input and lift banks — or a large processing plant on standby. Above this load, the usual answer is not a bigger set but two synchronised 750s: an N+1 pair survives a set failure, a single larger set does not.

Does the 750 kVA CPCB IV+ set use DEF (AdBlue)?

Yes. The CI 750D5P meets CPCB IV+ with SCR after-treatment using AUS 32 (DEF) per ISO 22241, fed from a 139 litre on-board tank. On rentals we manage DEF top-ups as part of scheduled service; on owned sets we train your operator on consumption and quality — wrong or diluted DEF is a warrantable failure.

What does it take to place a 750 kVA set on site?

This is trailer-and-crane territory — the CI 750D5P’s enclosure runs 6.8 m and roughly 10,200 kg wet — so we plan the crane day, cable runs and (where applicable) synchronisation panels as part of the deployment, not as surprises. Site survey, delivery, commissioning and scheduled B-checks are all included.