DG Rental · 750 kVA
750 kVA Diesel Generator on Rent
An IT campus building — chillers, UPS input and lift banks — on a single 750 kVA set.
What it powers
An IT campus building — chillers, UPS input and lift banks — on a single 750 kVA set.
A large cold store or food-processing plant on round-the-clock standby.
Paired and synchronised for loads that have outgrown any single mid-range rating.
Size for starting current, not running load — direct-on-line motor starting draws six to seven times full-load current. Send us your load list and we size it free of charge.
Specification
Genset
- Model
- CI 750D5P
- Prime rating
- 750 kVA / 600 kWe
- Full-load current
- 1,043 A
- Voltage · frequency
- 415 V · 50 Hz
- Phases · power factor
- 3-phase · 0.8 PF
- Speed
- 1,500 RPM
- Emission norm
- CPCB IV+
- Controller
- PS0602 with AMF
Engine
- Make · model
- Cummins QSK19-G30
- Certified power
- 888 HP
- Cylinders
- 6, In-line
- Bore × stroke
- 159 × 159 mm
- Displacement
- 19 L
- Compression ratio
- 14.7:1
- Aspiration
- Turbocharged, Charge Air Cooled
- Cooling
- Liquid Cooled (EG Compleat 50:50)
- Fuel
- High Speed Diesel
- DEF
- AUS 32 (Premix) as per ISO 22241
- Starting system
- 24 V DC Electrical
- Lube oil spec
- CK4
- Coolant capacity
- 95 L
- Performance class
- ISO 8528-5 G2
Alternator
- Make
- STAMFORD (CGT)
- Frame
- HCI634W
- Enclosure · insulation
- IP 23 · Class H
- Voltage regulation
- ±1%
- Winding pitch
- 2/3
Acoustic enclosure
- Dimensions (L × W × H)
- 6,800 × 2,050 × 2,900 mm
- Wet weight
- 10,200 kg
- Fuel tank
- 990 L
- DEF tank
- 139 L
- Noise level
- 75 dBA (1 m, 75% load, free-field (MoEF/CPCB))
Transcribed from the Cummins India specification sheet for the CI 750D5P. Ratings are prime power per ISO 8528; site conditions can derate output — confirm against your load list.
Rental, the way we run it
Rates move with tenure, site and season — so we quote same-day, not never.
- Acoustic-enclosed set, delivered and commissioned
- Scheduled B-check maintenance every 250–300 running hours, included
- 4–6-hour breakdown response on live contracts
Deposits, lock-ins and the standby clause are on the rental terms page — no surprises at work-order stage.
750 kVA, answered
Frequently asked questions
What does a 750 kVA generator run?
A 750 kVA (600 kW) set carries an IT campus building — chillers, UPS input and lift banks — or a large processing plant on standby. Above this load, the usual answer is not a bigger set but two synchronised 750s: an N+1 pair survives a set failure, a single larger set does not.
Does the 750 kVA CPCB IV+ set use DEF (AdBlue)?
Yes. The CI 750D5P meets CPCB IV+ with SCR after-treatment using AUS 32 (DEF) per ISO 22241, fed from a 139 litre on-board tank. On rentals we manage DEF top-ups as part of scheduled service; on owned sets we train your operator on consumption and quality — wrong or diluted DEF is a warrantable failure.
What does it take to place a 750 kVA set on site?
This is trailer-and-crane territory — the CI 750D5P’s enclosure runs 6.8 m and roughly 10,200 kg wet — so we plan the crane day, cable runs and (where applicable) synchronisation panels as part of the deployment, not as surprises. Site survey, delivery, commissioning and scheduled B-checks are all included.