DG Rental · 500 kVA
500 kVA Diesel Generator on Rent
A large factory's full production load run as prime power, day after day, outage after outage.
What it powers
A large factory's full production load run as prime power, day after day, outage after outage.
An IT floor plus precision-cooled server rooms carried through utility failures.
A construction project's tower cranes, batching plant and site utilities on a single set.
Size for starting current, not running load — direct-on-line motor starting draws six to seven times full-load current. Send us your load list and we size it free of charge.
Specification
Genset
- Model
- CI 500D5P
- Prime rating
- 500 kVA / 400 kWe
- Full-load current
- 695.6 A
- Voltage · frequency
- 415 V · 50 Hz
- Phases · power factor
- 3-phase · 0.8 PF
- Speed
- 1,500 RPM
- Emission norm
- CPCB IV+
- Controller
- PS0602 with AMF
Engine
- Make · model
- Cummins QSM15-G1
- Certified power
- 594 HP
- Cylinders
- 6, In-line
- Bore × stroke
- 135 × 169 mm
- Displacement
- 14.5 L
- Compression ratio
- 23:1
- Aspiration
- Turbocharged, Charge Air Cooled
- Cooling
- Liquid Cooled (EG Compleat 50:50)
- Fuel
- High Speed Diesel
- DEF
- AUS 32 (Premix) as per ISO 22241
- Starting system
- 24 V DC Electrical
- Lube oil spec
- CK4
- Coolant capacity
- 67 L
- Performance class
- ISO 8528-5 G2
Alternator
- Make
- STAMFORD (CGT)
- Frame
- HCI544D
- Enclosure · insulation
- IP 23 · Class H
- Voltage regulation
- ±1%
- Winding pitch
- 2/3
Acoustic enclosure
- Dimensions (L × W × H)
- 5,300 × 1,900 × 2,490 mm
- Wet weight
- 5,915 kg
- Fuel tank
- 745 L
- DEF tank
- 87 L
- Noise level
- 75 dBA (1 m, 75% load, free-field (MoEF/CPCB))
Transcribed from the Cummins India specification sheet for the CI 500D5P. Ratings are prime power per ISO 8528; site conditions can derate output — confirm against your load list.
Rental, the way we run it
Rates move with tenure, site and season — so we quote same-day, not never.
- Acoustic-enclosed set, delivered and commissioned
- Scheduled B-check maintenance every 250–300 running hours, included
- 4–6-hour breakdown response on live contracts
Deposits, lock-ins and the standby clause are on the rental terms page — no surprises at work-order stage.
500 kVA, answered
Frequently asked questions
What does a 500 kVA generator run?
A 500 kVA (400 kW) set is the workhorse of large-site rental: a factory’s full production load as prime power, an IT floor with precision cooling, or a construction project’s cranes and batching plant. It is the single most quoted rating in the Indian rental market — which is exactly why sizing against your actual load list, not the market default, matters.
Does the 500 kVA CPCB IV+ set use DEF (AdBlue)?
Yes. The CI 500D5P meets CPCB IV+ with SCR after-treatment using AUS 32 (DEF) per ISO 22241, fed from a 87 litre on-board tank. On rentals we manage DEF top-ups as part of scheduled service; on owned sets we train your operator on consumption and quality — wrong or diluted DEF is a warrantable failure.
What does it take to place a 500 kVA set on site?
This is trailer-and-crane territory — the CI 500D5P’s enclosure runs 5.3 m and roughly 5,915 kg wet — so we plan the crane day, cable runs and (where applicable) synchronisation panels as part of the deployment, not as surprises. Site survey, delivery, commissioning and scheduled B-checks are all included.