Specification
Genset
- Model
- CI 82.5D5P
- Prime rating
- 82.5 kVA / 66 kWe
- Full-load current
- 115 A
- Voltage · frequency
- 415 V · 50 Hz
- Phases · power factor
- 3-phase · 0.8 PF
- Speed
- 1,500 RPM
- Emission norm
- CPCB IV+
- Controller
- PS0602 with AMF
Engine
- Make · model
- Cummins QSB4.5-G1
- Certified power
- 132 HP
- Cylinders
- 4, In-line
- Bore × stroke
- 107 × 124 mm
- Displacement
- 4.5 L
- Compression ratio
- 17.3:1
- Aspiration
- Turbocharged, Charge Air Cooled
- Cooling
- Liquid Cooled (EG Compleat 50:50)
- Fuel
- High Speed Diesel
- DEF
- AUS 32 (Premix) as per ISO 22241
- Starting system
- 24 V DC Electrical
- Lube oil spec
- CK4
- Coolant capacity
- 20.2 L
- Performance class
- ISO 8528-5 G2
Alternator
- Make
- STAMFORD (CGT)
- Frame
- S2L1D-G41
- Enclosure · insulation
- IP 23 · Class H
- Voltage regulation
- ±0.5%
- Winding pitch
- 2/3
Acoustic enclosure
- Dimensions (L × W × H)
- 3,500 × 1,150 × 1,850 mm
- Wet weight
- 2,193 kg
- Fuel tank
- 260 L
- DEF tank
- 60 L
- Noise level
- 75 dBA (1 m, 75% load, free-field (MoEF/CPCB))
Transcribed from the Cummins India specification sheet for the CI 82.5D5P. Ratings are prime power per ISO 8528; site conditions can derate output — confirm against your load list.
Rental, the way we run it
Rates move with tenure, site and season — so we quote same-day, not never.
- Acoustic-enclosed set, delivered and commissioned
- Scheduled B-check maintenance every 250–300 running hours, included
- 4–6-hour breakdown response on live contracts
Deposits, lock-ins and the standby clause are on the rental terms page — no surprises at work-order stage.
82.5 kVA, answered
Frequently asked questions
What does a 82.5 kVA generator run?
An 82.5 kVA (66 kW) set runs a 20,000–30,000 sq ft warehouse with dock levellers and charging bays, a commercial floor with two lifts and HVAC, or a cold-room cluster. It is the step up when a 62.5 kVA set leaves no starting headroom for the largest motor on site.
Does the 82.5 kVA CPCB IV+ set use DEF (AdBlue)?
Yes. The CI 82.5D5P meets CPCB IV+ with SCR after-treatment using AUS 32 (DEF) per ISO 22241, fed from a 60 litre on-board tank. On rentals we manage DEF top-ups as part of scheduled service; on owned sets we train your operator on consumption and quality — wrong or diluted DEF is a warrantable failure.
How is a 82.5 kVA rental set delivered and installed?
The CI 82.5D5P travels on a light commercial vehicle — the enclosure is 3.5 m long and weighs about 2,193 kg wet — so most sites need only a level hardstand and cable route, no crane. Delivery, positioning, commissioning and scheduled B-checks every 250–300 running hours are included in the rental.
Related