GSTIN 27ANQPP7409M1Z5 · Pan-India service · HQ Pune [email protected] ☎ +91 86054 45290

DG Rental · 82.5 kVA

82.5 kVA Diesel Generator on Rent

A 20,000–30,000 sq ft warehouse — dock levellers, charging bays and high-bay lighting — through an outage.

Rating82.5 kVA / 66 kWe
ModelCI 82.5D5P
Emission normCPCB IV+
Noise75 dBA @ 1 m

What it powers

A 20,000–30,000 sq ft warehouse — dock levellers, charging bays and high-bay lighting — through an outage.

A cold-room cluster holding temperature while the grid decides whether to come back.

A commercial floor with two lifts, common HVAC and emergency systems together.

Size for starting current, not running load — direct-on-line motor starting draws six to seven times full-load current. Send us your load list and we size it free of charge.

Specification

Genset

Model
CI 82.5D5P
Prime rating
82.5 kVA / 66 kWe
Full-load current
115 A
Voltage · frequency
415 V · 50 Hz
Phases · power factor
3-phase · 0.8 PF
Speed
1,500 RPM
Emission norm
CPCB IV+
Controller
PS0602 with AMF

Engine

Make · model
Cummins QSB4.5-G1
Certified power
132 HP
Cylinders
4, In-line
Bore × stroke
107 × 124 mm
Displacement
4.5 L
Compression ratio
17.3:1
Aspiration
Turbocharged, Charge Air Cooled
Cooling
Liquid Cooled (EG Compleat 50:50)
Fuel
High Speed Diesel
DEF
AUS 32 (Premix) as per ISO 22241
Starting system
24 V DC Electrical
Lube oil spec
CK4
Coolant capacity
20.2 L
Performance class
ISO 8528-5 G2

Alternator

Make
STAMFORD (CGT)
Frame
S2L1D-G41
Enclosure · insulation
IP 23 · Class H
Voltage regulation
±0.5%
Winding pitch
2/3

Acoustic enclosure

Dimensions (L × W × H)
3,500 × 1,150 × 1,850 mm
Wet weight
2,193 kg
Fuel tank
260 L
DEF tank
60 L
Noise level
75 dBA (1 m, 75% load, free-field (MoEF/CPCB))

Transcribed from the Cummins India specification sheet for the CI 82.5D5P. Ratings are prime power per ISO 8528; site conditions can derate output — confirm against your load list.

Rental, the way we run it

Rates move with tenure, site and season — so we quote same-day, not never.

  • Acoustic-enclosed set, delivered and commissioned
  • Scheduled B-check maintenance every 250–300 running hours, included
  • 4–6-hour breakdown response on live contracts

82.5 kVA, answered

Frequently asked questions

What does a 82.5 kVA generator run?

An 82.5 kVA (66 kW) set runs a 20,000–30,000 sq ft warehouse with dock levellers and charging bays, a commercial floor with two lifts and HVAC, or a cold-room cluster. It is the step up when a 62.5 kVA set leaves no starting headroom for the largest motor on site.

Does the 82.5 kVA CPCB IV+ set use DEF (AdBlue)?

Yes. The CI 82.5D5P meets CPCB IV+ with SCR after-treatment using AUS 32 (DEF) per ISO 22241, fed from a 60 litre on-board tank. On rentals we manage DEF top-ups as part of scheduled service; on owned sets we train your operator on consumption and quality — wrong or diluted DEF is a warrantable failure.

How is a 82.5 kVA rental set delivered and installed?

The CI 82.5D5P travels on a light commercial vehicle — the enclosure is 3.5 m long and weighs about 2,193 kg wet — so most sites need only a level hardstand and cable route, no crane. Delivery, positioning, commissioning and scheduled B-checks every 250–300 running hours are included in the rental.

Related

Reply within 4 working hours. Engineered offer within 24 hours.