DG Rental · 40 kVA
40 kVA Diesel Generator on Rent
A QSR outlet at service peak — fryers, freezers and dining HVAC — without a flicker at the counter.
What it powers
A QSR outlet at service peak — fryers, freezers and dining HVAC — without a flicker at the counter.
A fuel station's dispensers, canopy lighting and payment systems through an outage.
A clinic with refrigerated vaccine storage and lab equipment that cannot see a warm hour.
Size for starting current, not running load — direct-on-line motor starting draws six to seven times full-load current. Send us your load list and we size it free of charge.
Specification
Genset
- Model
- CI 40D5P
- Prime rating
- 40 kVA / 32 kWe
- Full-load current
- 56 A
- Voltage · frequency
- 415 V · 50 Hz
- Phases · power factor
- 3-phase · 0.8 PF
- Speed
- 1,500 RPM
- Emission norm
- CPCB IV+
- Controller
- PS0602 with AMF
Engine
- Make · model
- Cummins X2.6-G2
- Certified power
- 53.1 HP
- Cylinders
- 3, In-line
- Bore × stroke
- 93 × 127 mm
- Displacement
- 2.59 L
- Compression ratio
- 17:1
- Aspiration
- Turbocharged, Intercooled
- Cooling
- Liquid Cooled (EG Compleat 50:50)
- Fuel
- High Speed Diesel
- Starting system
- 12 V DC Electrical
- Lube oil spec
- CK4
- Coolant capacity
- 10.2 L
- Performance class
- ISO 8528-5 G2
Alternator
- Make
- STAMFORD (CGT)
- Frame
- S2L1D-C41
- Enclosure · insulation
- IP 23 · Class H
- Voltage regulation
- ±0.5%
- Winding pitch
- 2/3
Acoustic enclosure
- Dimensions (L × W × H)
- 2,400 × 950 × 1,400 mm
- Wet weight
- 1,090 kg
- Fuel tank
- 102 L
- Noise level
- 75 dBA (1 m, 75% load, free-field (MoEF/CPCB))
Transcribed from the Cummins India specification sheet for the CI 40D5P. Ratings are prime power per ISO 8528; site conditions can derate output — confirm against your load list.
Rental, the way we run it
Rates move with tenure, site and season — so we quote same-day, not never.
- Acoustic-enclosed set, delivered and commissioned
- Scheduled B-check maintenance every 250–300 running hours, included
- 4–6-hour breakdown response on live contracts
Deposits, lock-ins and the standby clause are on the rental terms page — no surprises at work-order stage.
40 kVA, answered
Frequently asked questions
What does a 40 kVA generator run?
A 40 kVA (32 kW) prime-rated set carries a QSR outlet at service peak, a fuel station’s dispensers and canopy systems, or a clinic with refrigerated storage and lab equipment. With 56 A of full-load current it handles small mixed commercial loads with a compressor or two in the mix.
Does the 40 kVA CPCB IV+ set need DEF (AdBlue)?
No. The CI 40D5P meets CPCB IV+ through in-cylinder combustion control and a diesel oxidation catalyst — there is no SCR system and no DEF tank at this rating. That is one less consumable to manage and one less thing to get wrong on site.
How is a 40 kVA rental set delivered and installed?
The CI 40D5P travels on a light commercial vehicle — the enclosure is 2.4 m long and weighs about 1,090 kg wet — so most sites need only a level hardstand and cable route, no crane. Delivery, positioning, commissioning and scheduled B-checks every 250–300 running hours are included in the rental.