DG Rental · 40 kVA

40 kVA Diesel Generator on Rent

A QSR outlet at service peak — fryers, freezers and dining HVAC — without a flicker at the counter.

Rating40 kVA / 32 kWe
ModelCI 40D5P
Emission normCPCB IV+
Noise75 dBA @ 1 m

What it powers

A QSR outlet at service peak — fryers, freezers and dining HVAC — without a flicker at the counter.

A fuel station's dispensers, canopy lighting and payment systems through an outage.

A clinic with refrigerated vaccine storage and lab equipment that cannot see a warm hour.

Size for starting current, not running load — direct-on-line motor starting draws six to seven times full-load current. Send us your load list and we size it free of charge.

Specification

Genset

Model
CI 40D5P
Prime rating
40 kVA / 32 kWe
Full-load current
56 A
Voltage · frequency
415 V · 50 Hz
Phases · power factor
3-phase · 0.8 PF
Speed
1,500 RPM
Emission norm
CPCB IV+
Controller
PS0602 with AMF

Engine

Make · model
Cummins X2.6-G2
Certified power
53.1 HP
Cylinders
3, In-line
Bore × stroke
93 × 127 mm
Displacement
2.59 L
Compression ratio
17:1
Aspiration
Turbocharged, Intercooled
Cooling
Liquid Cooled (EG Compleat 50:50)
Fuel
High Speed Diesel
Starting system
12 V DC Electrical
Lube oil spec
CK4
Coolant capacity
10.2 L
Performance class
ISO 8528-5 G2

Alternator

Make
STAMFORD (CGT)
Frame
S2L1D-C41
Enclosure · insulation
IP 23 · Class H
Voltage regulation
±0.5%
Winding pitch
2/3

Acoustic enclosure

Dimensions (L × W × H)
2,400 × 950 × 1,400 mm
Wet weight
1,090 kg
Fuel tank
102 L
Noise level
75 dBA (1 m, 75% load, free-field (MoEF/CPCB))

Transcribed from the Cummins India specification sheet for the CI 40D5P. Ratings are prime power per ISO 8528; site conditions can derate output — confirm against your load list.

Rental, the way we run it

Rates move with tenure, site and season — so we quote same-day, not never.

  • Acoustic-enclosed set, delivered and commissioned
  • Scheduled B-check maintenance every 250–300 running hours, included
  • 4–6-hour breakdown response on live contracts

40 kVA, answered

Frequently asked questions

What does a 40 kVA generator run?

A 40 kVA (32 kW) prime-rated set carries a QSR outlet at service peak, a fuel station’s dispensers and canopy systems, or a clinic with refrigerated storage and lab equipment. With 56 A of full-load current it handles small mixed commercial loads with a compressor or two in the mix.

Does the 40 kVA CPCB IV+ set need DEF (AdBlue)?

No. The CI 40D5P meets CPCB IV+ through in-cylinder combustion control and a diesel oxidation catalyst — there is no SCR system and no DEF tank at this rating. That is one less consumable to manage and one less thing to get wrong on site.

How is a 40 kVA rental set delivered and installed?

The CI 40D5P travels on a light commercial vehicle — the enclosure is 2.4 m long and weighs about 1,090 kg wet — so most sites need only a level hardstand and cable route, no crane. Delivery, positioning, commissioning and scheduled B-checks every 250–300 running hours are included in the rental.

Related