DG Rental · 1250 kVA

1250 kVA Diesel Generator on Rent

A continuous-process plant where even a controlled stop costs a full batch.

Rating1250 kVA / 1000 kWe
ModelC1250D5P
Emission normMoEFCC >800 kW
EngineKTA 50 G3

What it powers

A continuous-process plant where even a controlled stop costs a full batch.

Campus central plants — chiller banks, STPs and common infrastructure on one bus.

The largest single-set rating in the fleet before parallel banks take over.

Size for starting current, not running load — direct-on-line motor starting draws six to seven times full-load current. Send us your load list and we size it free of charge.

Specification

Genset

Model
C1250D5P
Prime rating
1250 kVA / 1000 kWe
Voltage · frequency
415 V · 50 Hz
Phases · power factor
3-phase · 0.8 PF
Speed
1,500 RPM
Emission norm
MoEFCC >800 kW
Controller
PCC3.3 with AMF

Engine

Make · model
Cummins KTA 50 G3
Certified power
1,470 HP
Cylinders
16, 'Vee'
Bore × stroke
159 × 159 mm
Displacement
50.3 L
Compression ratio
13.9:1
Aspiration
Turbocharged-Aftercooled
Cooling
Water cooled (Radiator or heat exchanger, coolant inhibitor)
Fuel
High Speed Diesel
Starting system
Electric starting motor, battery charging alternator; 4 x 12 V dry uncharged batteries
Coolant capacity
440 L

Alternator

Make
Stamford
Frame
HCK6Z
Enclosure · insulation
IP 23 · Class H
Voltage regulation
+ 0.5%
Winding pitch
2 / 3 Pitch

Open genset dimensions

Dimensions (L × W × H)
5,212 × 2,179 × 3,001 mm
Wet weight
11,235 kg
Fuel tank
990 L

Fuel consumption

At 75% load
190.8 L/hr
At 100% load
251.8 L/hr

Source: Cummins specification sheet for the C1250D5P · rev. 07-2018. Diesel SG 0.85 per IS:1460; tolerance +5%. Actual consumption varies with load profile and site conditions.

Transcribed from the Cummins India specification sheet for the C1250D5P. Ratings are prime power per ISO 8528; site conditions can derate output — confirm against your load list. Dimensions are for the open set; acoustic treatment is engineered per site.

Rental, the way we run it

Rates move with tenure, site and season — so we quote same-day, not never.

  • Set delivered, positioned and commissioned — acoustic treatment engineered per site
  • Scheduled B-check maintenance every 250–300 running hours, included
  • 4–6-hour breakdown response on live contracts

1250 kVA, answered

Frequently asked questions

What does a 1250 kVA generator run?

A 1250 kVA (1000 kW) set carries continuous-process plants and campus central infrastructure — chiller banks, STPs, house power — on a single bus. Beyond this, requirements move to synchronised multi-set banks, which we engineer and operate as turnkey deployments.

Is the 1250 kVA set CPCB IV+ compliant?

CPCB IV+ applies to gensets with engines up to 800 kW — the C1250D5P’s engine is above that threshold, so it is governed by the MoEFCC’s separate emission standards for >800 kW diesel engines, not CPCB IV+. It is fully legal to deploy on rental; stack height, siting and consent conditions are engineered into the deployment, and we advise on state-specific requirements where they apply.

What does it take to place a 1250 kVA set on site?

This is trailer-and-crane territory — the C1250D5P’s open set runs 5.2 m and roughly 11,235 kg wet — so we plan the crane day, cable runs, acoustic treatment and (where applicable) synchronisation panels as part of the deployment, not as surprises. Site survey, delivery, commissioning and scheduled B-checks are all included.

Related

Reply within 4 working hours. Engineered offer within 24 hours.